High Voltage Apparatus Bushing Creepage


The minimum bushing creepage required for the areas with different contamination levels is well defined in IEEE Std C57.19.100.

The areas with contamination levels light, medium, heavy and extra heavy are defined in Table 1 of the above document as follows:

Light:

Areas without industries and with a low density of emission-producing residential heating systems. Areas with some industrial or residential density but subject to frequent winds and/or precipitation. Agricultural areas (exposure to wind-borne fertilizer spray or crop-burning residues can lead to higher contamination levels).Mountainous areas. 

These areas are not exposed to sea winds or located near the sea. Typical measured equivalent salt deposit density (ESDD) levels are 0.03 mg/cm2 to 0.08 mg/cm2.

Medium:

Areas with industries not producing highly polluting smoke and/or with an average density of emission-producing residential heating systems. Areas with high industrial and/or residential density but subject to frequent winds and/or precipitation. Areas exposed to sea winds but not located directly on the coast. Typical measured ESDD levels are 0.08 mg/cm2 to 0.25 mg/cm2.

Heavy:

Areas with high industrial density and large city suburbs with a high density of emission-producing residential heating systems. Areas close to the sea or exposed to strong sea winds. Typical measured ESDD levels are 0.25 mg/cm2 to 0.6 mg/cm2.

Extra heavy:

Small areas subject to industrial smoke-producing thick conductive deposits. Small coastal areas exposed to very strong and polluting sea winds. Typical measured ESDD levels are above 0.6 mg/cm2.

The minimum creep values based on the nominal line to ground kV rating are recommended in the clause 9.1.5 of IEEE Std C57.19.100 as follows:

Contamination          Creep distance
Light                            28 mm/kV
Medium                       35 mm/kV
Heavy                          44 mm/kV
Extra heavy                 54 mm/kV or greater

Below is a list of other measures recommended in the IEEE document to mitigate the risk of flashover in the contaminated areas:

·         Application of protective coating to improve dielectric performance.
·         Installation of conductive glaze bushings.
·         Installation of contamination-resistant composite insulated bushings.
·         Periodic Cleaning of the bushing surface.
·         Design change to minimize the number of outdoor bushings.





Masoud Kashani
Substation Engineer – New York, Brightline BES Program

 AVANGRID Networks Inc.
1300 Scottsville Rd., Rochester, NY, 14624
Telephone  585.771.4396
 
masoud_kashani@rge.com


In the interest of the environment,
please print only if necessary and recycle.



==============================================================      Please consider the environment before printing this email.    If you have received this message in error, please notify the sender and immediately delete this message and any attachment hereto and/or copy hereof, as such message contains confidential information intended solely for the individual or entity to whom it is addressed. The use or disclosure of such information to third parties is prohibited by law and may give rise to civil or criminal liability.    The views presented in this message are solely those of the author(s) and do not necessarily represent the opinion of Avangrid, Inc. or any company of its group. Neither Avangrid, Inc. nor any company of its group guarantees the integrity, security or proper receipt of this message. Likewise, neither Avangrid, Inc. nor any company of its group accepts any liability whatsoever for any possible damages arising from, or in connection with, data interception, software viruses or manipulation by third parties.     ==============================================================

No comments:

Post a Comment